NGH provided Parallel A/B redundant -48V 1500A modular, scalable, Titan II DC plants by C&D Technologies, with integrated DC distribution sections and TCP/IP monitoring. Multiple parallel redundant C&D Technologies msEndur II VRLA battery strings, with over 17,000AH of combined capacity with integral EPO enabled battery disconnect circuit breakers and Enviroguard battery spill containment systems. DSPM Defender III, 20kVA UL924 Emergency Lighting Inverter with external MBP and monitoring. PDI 75kVA primary static switch power distribution units, with Wavestar monitoring system. PDI 150kVA redundant power distribution system with Wavestar monitoring system. NGH also provided battery installation, and completed the project with load bank testing, IEEE-1188 and IEEE-450 battery capacity testing and IR thermography.